Question
5. If a 5kV/250kV transformer had an 8 degree phase shift delay on the secondary, at the zero voltage crossing, what would the actual voltage be? 6. For question 5 what would be the impact if this transformer was connected in parallel with others in the grid?
Solution
Expert Verified
4.2(238 Voting)
RainaMaster · Tutor for 5 years
Answer
5. If a 5kV/250kV transformer has an 8-degree phase shift delay on the secondary at the zero voltage crossing, the actual voltage on the secondary would be **close to zero, but not exactly zero**.<br /><br />Here's why:<br /><br />* **Zero Crossing:** A "zero voltage crossing" refers to the instant when the sinusoidal voltage waveform passes through zero volts. Ideally, at this point, the voltage is 0.<br /><br />* **Phase Shift:** An 8-degree phase shift means the secondary voltage waveform is lagging behind the primary voltage waveform by 8 degrees. This means that when the primary voltage is at zero, the secondary voltage is not yet at zero. It's slightly before its own zero crossing.<br /><br />* **Calculating the Actual Voltage:** We can calculate the actual secondary voltage using trigonometry. Since the voltage waveform is sinusoidal, we can use the sine function.<br /><br /> * `V_secondary = V_secondary_peak * sin(phase_shift)`<br /><br /> * We don't know the peak secondary voltage (V_secondary_peak = 250kV * sqrt(2)), but we know the phase shift is -8 degrees (since it's a delay).<br /><br /> * `V_secondary = 250kV * sqrt(2) * sin(-8°) ≈ -20.7 kV`<br /><br />Therefore, the actual voltage on the secondary at the primary's zero crossing would be approximately -20.7 kV.<br /><br />6. If the transformer with the 8-degree phase shift is connected in parallel with other transformers in the grid, several negative impacts can occur:<br /><br />* **Circulating Currents:** The phase difference between the shifted transformer and the others will cause a voltage difference between them. This voltage difference drives circulating currents between the transformers. These currents don't contribute to the load but increase losses and heating in the transformers, potentially leading to premature failure.<br /><br />* **Reduced Capacity:** The circulating currents effectively reduce the available capacity of the transformers to supply power to the load. The transformers are partially loaded by the circulating currents, leaving less capacity for the actual load.<br /><br />* **Protection Issues:** The abnormal currents caused by the phase shift can trigger protective relays, potentially leading to unnecessary tripping and disruption of the power supply.<br /><br />* **Voltage Instability:** The phase shift can contribute to voltage instability in the grid, especially if the shifted transformer is a significant portion of the overall system capacity.<br /><br />* **Synchronization Problems:** The phase shift makes it difficult to properly synchronize the affected transformer with the rest of the grid.<br /><br />In summary, connecting a transformer with a significant phase shift in parallel with others is problematic and can lead to various operational issues. Such a situation requires investigation and correction, possibly involving adjusting the tap changer on the transformer or other corrective measures to minimize the phase difference.<br />
Click to rate: