Question
5. If a 5kV/250kV transformer had an 8 degree phase shift delay on the secondary, at the zero voltage crossing, what would the actual voltage be?
Solution
Expert Verified
4.6(253 Voting)
StuartVeteran · Tutor for 9 years
Answer
Here's how to calculate the actual voltage on the secondary side of the transformer at the zero voltage crossing, considering the phase shift:<br /><br />**Understanding the Problem**<br /><br />A zero voltage crossing refers to the instant when the voltage waveform passes through zero volts. Ideally, both primary and secondary would cross zero at the same time. However, the phase shift introduces a time delay between the primary and secondary zero crossings. This means that when the primary voltage is at zero, the secondary voltage is *not* at zero.<br /><br />**Calculations**<br /><br />1. **Convert Phase Shift to Time Delay:**<br /><br /> We know the frequency of the power system is 60Hz (this is standard in most regions, and it's a reasonable assumption if the frequency isn't specified). The period (T) of one cycle is 1/60 seconds, or approximately 16.67 milliseconds.<br /><br /> An 8-degree phase shift represents a fraction of the total cycle:<br /><br /> (8 degrees / 360 degrees) = 0.0222 of a cycle<br /><br /> The time delay (Δt) is this fraction multiplied by the period:<br /><br /> Δt = 0.0222 * 16.67 ms ≈ 0.37 ms<br /><br />2. **Determine the Rate of Voltage Change:**<br /><br /> We need to know how quickly the voltage is changing around the zero crossing. For a sinusoidal waveform, the voltage changes most rapidly as it crosses zero. We can approximate this rate of change by looking at the slope of the sine wave at the zero crossing.<br /><br /> The instantaneous voltage of a sine wave is given by:<br /><br /> V(t) = V_peak * sin(ωt) <br /><br /> where ω is the angular frequency (2πf) and V_peak is the peak voltage.<br /><br /> The derivative of this gives the rate of change:<br /><br /> dV/dt = V_peak * ω * cos(ωt)<br /><br /> At the zero crossing (ωt = 0 or π), cos(ωt) = 1 or -1, so the rate of change is approximately:<br /><br /> dV/dt = ±V_peak * ω<br /><br />3. **Calculate the Secondary Voltage at the Zero Crossing:**<br /><br /> The secondary voltage at the zero crossing can be estimated by multiplying the rate of change by the time delay:<br /><br /> V_secondary_at_zero_crossing ≈ (dV/dt) * Δt<br /><br /> We need the peak voltage on the secondary. Assuming the transformer ratio is based on RMS values, the secondary RMS voltage is 250 kV. The peak voltage is √2 times the RMS voltage:<br /><br /> V_peak_secondary = √2 * 250 kV ≈ 353.55 kV<br /><br /> Now we can calculate the voltage:<br /><br /> V_secondary_at_zero_crossing ≈ (353.55 kV * 2π * 60 Hz) * 0.37 ms <br /> V_secondary_at_zero_crossing ≈ 49.2 kV<br /><br />**Answer:**<br /><br />The actual voltage on the secondary side at the primary's zero voltage crossing would be approximately 49.2 kV.<br /><br />**Important Note:** This calculation uses an approximation for the rate of voltage change. A more precise calculation would require integrating the sine wave over the small time interval of the delay. However, for practical purposes, this approximation is usually sufficient.<br />
Click to rate: